480V 3Phase Input
|
|
Output (DC)
|
|
Nominal output power
|
60W
|
120W
|
240W
|
480W
|
|
Nominal output voltage UN / tolerance
|
24 VDC ± 2 %
|
24 VDC ± 2 %
|
24 VDC ± 2 %
|
24 VDC ± 2 %
|
|
Adjustment range of the voltage
|
22-28 VDC
|
22-28 VDC
|
22-28 VDC
|
22-28 VDC
|
|
Nominal current
|
2.5 A
|
5A
|
10A
|
20 A
|
|
Derating above +50 °C
|
2.5 % / K.
|
2.5 % / K.
|
2.5 % / K. (> 70 °C 4% / K.)
|
2.5 % / K.
|
|
Startup with capacitive loads
|
Max. 10,000 μF
|
Max. 10,000 μF
|
Max. 10,000 μF
|
Max. 10,000 μF
|
|
Max. power dissipation idling / nominal load approx.
|
9 W
|
18 W
|
36 W
|
72 W
|
|
Efficiency (at 400V AC and nominal values)
|
> 86% @ 3 x 400 VAC, > 85% @ 3 x 500 VAC
|
> 86% @ 3 x 400 VAC, > 85% @ 3 x 500 VAC
|
>87% @ 3 x 400 VAC, > 86 % @ 3 x 500 VAC
|
> 87 % @ 3 x 400 VAC, > 86% @ 3 x 500 VAC
|
|
Residual ripple/ peak switching (20 MHz) (at nominal values)
|
< 50 mV / < 240 mVpp
|
< 50 mV / < 240 mVpp
|
< 50 mV / < 240 mVpp
|
< 50 mV / < 240 mVpp
|
|
Parallel operation
|
With oring diode
|
With oring diode
|
With oring diode
|
With oring diode
|
|
Input (AC)
|
|
Nominal input voltage
|
3 x 400-500 VAC
|
3 x 400-500 VAC
|
3 x 400-500 VAC
|
3 x 400-500 VAC
|
|
Voltage range
|
320-575 VAC (DC input range 450-800 VDC)
|
320-575 VAC (DC input range 450-800 VDC)
|
320-575 VAC (DC input range 450-800 VDC)
|
350-575 VAC (DC input range 450-800 VDC)
|
|
Frequency
|
47-63 Hz (0 Hz @ DC input)
|
47-63 Hz (0 Hz @ DC input)
|
47-63 Hz (0 Hz @ DC input)
|
47-63 Hz (0 Hz @ DC input)
|
|
Nominal current
|
0.3 A @ 400 VAC approx.
|
0.5 A @ 400 VAC approx.
|
0.8 A @ 400 VAC approx.
|
1.6 A @ 400 VAC approx.
|
|
Inrush current limitation. I2t (+25 °C) typ.
|
< 30 A @ 400 VAC
|
< 30 A @ 400 VAC
|
<40 A (typical) @ 400 VAC
|
<50 A @ 400 VAC
|
|
Mains buffering at nominal load (typ.)
|
> 30 ms @ 3 x 400 VAC, > 60 ms @ 3 x 500 VAC
|
> 35 ms @ 3 x 400 VAC, > 70 ms @ 3 x 500 VAC
|
> 35 ms @ 3 x 400 VAC , > 60 ms @ 3 x 500 VAC
|
> 20 ms @ 3 x 400 VAC, > 40 ms @ 3 x 500 VAC
|
|
Turn-on time
|
< 2 sec.
|
< 1 sec.
|
< 1 sec.
|
< 1 sec.
|
|
Internal fuse
|
3.15 AH / 500 V
|
3.15 AH / 500 V
|
3.15 AH / 500 V
|
3.15 AH / 500 V
|
|
Recommended backup fuse
|
3 x circuit breakers 6 A, 10 A or 16 A
|
3 x circuit breakers 6 A, 10 A or 16 A
|
3 x circuit breakers 6 A, 10 A or 16 A
|
3 x circuit breaker 6 A, 10 A or 16 A
|
|
Power circuit-breaker characteristic
|
B
|
B
|
B
|
B
|
|
Leakage current
|
< 3.5 mA
|
< 3.5 mA
|
< 3.5 mA
|
< 3.5 mA
|
|
General Data
|
|
Type of housing
|
Aluminium (Al5052)
|
Aluminium (Al5052)
|
Aluminium (Al5052)
|
Aluminium (Al5052)
|
|
Signals
|
Green LED DC OK
|
Green LED DC OK
|
Green LED DC OK
|
Green LED DC OK
|
|
MTBF
|
> 500,000 hrs.
|
> 500,000 hrs.
|
> 300,000 hrs.
|
> 300,000 hrs.
|
|
Dimensions (L x W x H)
|
121 mm x 70 mm x 118.5 mm
|
121 mm x 70 mm x 118.5 mm
|
121 mm x 85 mm x 120.5 mm
|
121 mm x 160 mm x 115 mm
|
|
Weight
|
0.56 kg
|
0.72 kg
|
0.99 kg
|
1.71 kg
|
|
Connection method
|
Screw connection
|
Screw connection
|
Screw connection
|
Screw connection
|
|
Stripping length
|
7 mm or use suitable lug to crimp
|
7 mm or use suitable lug to crimp
|
7 mm or use suitable lug to crimp
|
7 mm or use suitable lug to crimp
|
|
Operating temperature
|
-20 °C to +75°C (> 50°C derating)
|
-20 °C to +75 °C (> 50°C derating)
|
-20 °C to +75°C (> 50°C derating)
|
-20 °C to +75 °C (> 50°C derating)
|
|
Storage temperature
|
-25 °C to +85 °C
|
-25 °C to +85 °C
|
-25 °C to +85 °C
|
-25 °C to +85 °C
|
|
Humidity at +25 °C, no condensation
|
< 95 % RH
|
< 95 % RH
|
< 95 % RH
|
< 95 % RH
|
|
Vibration (operating)
|
10 to 150 Hz, 0.35 mm acc. 50 m / s², single
|
10 to 150 Hz, 0.35 mm acc. 50 m / s², single
|
10 to 150 Hz, 0.35 mm acc. 50 m / s², single
|
10 to 150 Hz, 0.35 mm acc. 50 m / s², single
|
|
amplitude (5 G max.) for 90 min. in each X, Y & Z
|
amplitude (5 G max.) for 90 min. in each X, Y & Z
|
amplitude (5 G max.) for 90 min. in each X, Y & Z
|
amplitude (5 G max.) for 90 min. in each X, Y & Z
|
|
directions, in acc. with IEC 68-2-6
|
directions, in acc. with IEC 68-2-6
|
directions, in acc. with IEC 68-2-6
|
directions, in acc. with IEC 68-2-6
|
|
Pollution degree
|
2
|
2
|
2
|
2
|
|
Climatic class
|
3K3 according to EN 60721
|
3K3 according to EN 60721
|
3K3 according to EN 60721
|
3K3 according to EN 60721
|
|
Certification and Standards
|
|
Electrical equipments of machines
|
EN 60204 (surge voltage category III)
|
EN 60204 (surge voltage category III)
|
EN 60204 (surge voltage category III)
|
EN 60204 (surge voltage category III)
|
|
Electrical safety (of information technology equipment)
|
CSA / IEC / EN / UL 60950-1 /
|
CSA / IEC / EN / UL 60950-1 /
|
CSA / IEC / EN / UL 60950-1 /
|
CSA / IEC / EN / UL 60950-1 /
|
|
CB scheme per IEC 60950-1 /
|
CB scheme per IEC 60950-1 /
|
CB scheme per IEC 60950-1 /
|
CB scheme per IEC 60950-1 /
|
|
UL / C-UL recognized UL 60950-1
|
UL / C-UL recognized UL 60950-1
|
UL / C-UL recognized UL 60950-1
|
UL / C-UL recognized UL 60950-1
|
|
German Safety
|
German Safety
|
German Safety
|
German Safety
|
|
Industrial control equipment
|
UL / C-UL Listed UL 508
|
UL / C-UL Listed UL 508
|
UL / C-UL Listed UL 508
|
UL / C-UL Listed UL 508
|
|
Electronic equipment for use in electrical power installations
|
EN 50178 (UDE 0160)
|
EN 50178 (UDE 0160)
|
EN 50178 (UDE 0160)
|
EN 50178 (UDE 0160)
|
|
Safety entry low voltage
|
PELV (EN 60204), SELV (EN 60950)
|
PELV (EN 60204), SELV (EN 60950)
|
PELV (EN 60204), SELV (EN 60950)
|
PELV (EN 60204), SELV (EN 60950)
|
|
Protection against electric shock
|
DIN 57100-410
|
DIN 57100-410
|
DIN 57100-410
|
DIN 57100-410
|
|
Limitation of mains harmonic currents
|
According to EN 61000-3-2
|
According to EN 61000-3-2
|
According to EN 61000-3-2
|
According to EN 61000-3-2
|
|
EMI / EMC
|
In conformance with EMC guideline 2004/108/EC
|
In conformance with EMC guideline 2004/108/EC
|
In conformance with EMC guideline 2004/108/EC
|
In conformance with EMC guideline 2004/108/EC
|
|
and low voltage directive 2006/95/EC
|
and low voltage directive 2006/95/EC
|
and low voltage directive 2006/95/EC
|
and low voltage directive 2006/95/EC
|
|
EMC (electromagnetic compatibility)
|
EMC (electromagnetic compatibility)
|
EMC (electromagnetic compatibility)
|
EMC (electromagnetic compatibility)
|
|
Immunity to interference according to EN 61000-6-2, EN 61000-4-2
|
Immunity to interference according to EN 61000-6-2, EN 61000-4-2
|
Immunity to interference according to EN 61000-6-2, EN 61000-4-2
|
Immunity to interference according to EN 61000-6-2, EN 61000-4-2
|
|
EN 61000-4-3 ... EN 61000-4-6
|
EN 61000-4-3 ... EN 61000-4-6
|
EN 61000-4-3 ... EN 61000-4-6
|
EN 61000-4-3 ... EN 61000-4-6
|
|
EN 61000-4-11
|
EN 61000-4-11
|
EN 61000-4-11
|
EN 61000-4-11
|
|
Noise emission according to EN 61000-6-3
|
Noise emission according to EN 61000-6-3
|
Noise emission according to EN 61000-6-3
|
Noise emission according to EN 61000-6-3
|
|
RoHS Compliant
|
Yes
|
Yes
|
Yes
|
Yes
|
|
Safety and Protection
|
|
Transient surge voltage protection
|
VARISTOR
|
VARISTOR
|
VARISTOR
|
VARISTOR
|
|
Current limitation at short-circuits approx.
|
Isurge = 150 % of Pomax typically
|
Isurge = 150 % of Pomax typically
|
Isurge = 150 % of Pomax typically
|
Isurge = 150 % of Pomax typically
|
|
Surge voltage protection against internal surge voltages
|
Yes
|
Yes
|
Yes
|
Yes
|
|
Isolation voltage:
|
|
|
|
|
|
Input / output (type test/routine test)
|
4 kVAC / 3 kVAC
|
4 kVAC / 3 kVAC
|
4 kVAC / 3 kVAC
|
4 kVAC / 3 kVAC
|
|
Input / PE (type test/routine test)
|
1.5 kVAC / 1.5 kVAC
|
1.5 kVAC / 1.5 kVAC
|
1.5 kVAC / 1.5 kVAC
|
1.5 kVAC / 1.5 kVAC
|
|
Output / PE (type test/routine test)
|
1.5 kVAC / 500 VAC
|
1.5 kVAC / 500 VAC
|
1.5 kVAC / 500 VAC
|
1.5 kVAC / 500 VAC
|
|
Protection degree
|
IPX0
|
IPX0
|
IPX0
|
IPX0
|
|
Safety class
|
Class I with PE connection
|
Class I with PE connection
|
Class I with PE connection
|
Class I with PE connection
|
|
Shock (in all directions)
|
30 G (300 m/s²) in all directions according to IEC 68-2-27
|
30 G (300 m/s²) in all directions according to IEC 68-2-27
|
30 G (300 m/s²) in all directions according to IEC 68-2-27
|
30 G (300 m/s²) in all directions according to IEC 68-2-27
|