DTB
Delta’s DTB series is equipped with relay, pulse, DC current and linear voltage signal output. This dual output temperature controller device is capable of executing heating and cooling controls simultaneously in a temperature control system while efficiently attaining the target temperature. The various built-in features and transmission structure ensures fast and stable transmission of data.
|
|
|
|
DTB Specifications
|
Input
|
|
Input Voltage
|
100 to 240VAC @ 50/60Hz
|
|
Operation Voltage Range
|
85% to 110% of rated voltage
|
|
Power Consumption
|
5VA max.
|
|
Input Type
|
0~50mV Analog Input
|
-999 ~ 9999
|
|
4~20mA Analog Input
|
-999 ~ 9999
|
|
0~20mA Analog Input
|
-999 ~ 9999
|
|
0V~10V Analog Input
|
-999 ~ 9999
|
|
0V~5V Analog Input
|
-999 ~ 9999
|
|
Platinum Resistance (Pt100)
|
-200 ~ 600oC
|
|
Platinum Resistance (JPt100)
|
-20 ~ 400oC
|
|
Thermocouple TXK type
|
-200 ~ 800oC
|
|
Thermocouple U type
|
-200 ~ 500oC
|
|
Thermocouple L type
|
-200 ~ 850oC
|
|
Thermocouple B type
|
100 ~ 1800oC
|
|
Thermocouple S type
|
0 ~ 1700oC
|
|
Thermocouple R type
|
0 ~ 1700oC
|
|
Thermocouple N type
|
-200 ~ 1300oC
|
|
Thermocouple E type
|
0 ~ 600oC
|
|
Thermocouple T type
|
-200 ~ 400oC
|
|
Thermocouple J type
|
-100 ~ 1200oC
|
|
Thermocouple K type
|
-200 ~ 1300oC
|
|
Output
|
|
Control Mode
|
PID, ON/OFF, Manual or PID program control (Ramp/Soak control)
|
|
Control Output 1
|
R: Relay output, SPDT (SPST: 1/16 DIN and 1/32 DIN size), Max load 250VAC, 5A resistive
|
|
V: Voltage pulse output, 14V +10?~ -20?(Max. 40mA)
|
|
C: DC current output , 4 ~ 20m A
|
|
L: Linear voltage output, 0~5V, 0~10Vdc
|
|
Control Output 2
|
R: Relay output, SPDT (SPST: 1/16 DIN and 1/32 DIN size), Max load 250VAC, 5A resistive
|
|
V: Voltage pulse output, 14V +10?~ -20?(Max. 40mA)
|
|
General
|
|
2 groups of outputs to auto-tuning 2 groups of PID parameters
|
|
Maximum 2 groups of alarm switches are available, with 18 alarm modes each
|
|
Sampling time of thermocouple/platinum RTD: 0.4 second/time; sampling time of analog input: 0.15 second/time
|
|
Programmable logic controller is able to set up 64 sets of temperature and control time
|
|
Dimensions (W×H)
|
DIN Rail mounted (60 x 96)
|
|
Memory Protection
|
EEPROM 4K bit (non-volatile memory (number of writes: 100,000)
|
|
Sampling Rate
|
Analog input: 150 msec/ per scan Thermocouple or Platinum RTD: 400 msec/per scan
|
|
RS-485 Communication
|
MODBUS ASCII / RTU communication protocol
|
|
Vibration Resistance
|
10 to 55Hz, 10m/s2 for 10min, each in X, Y and Z directions
|
|
Shock Resistance
|
Max. 300m/ s2, 3 times in each 3 axes, 6 directions
|
|
Ambient Temperature
|
0 oC to +50 oC
|
|
Storage Temperature
|
-20 oC to +65 oC
|
|
Altitude
|
2000m or less
|
|
Relative Humidity
|
35% to 80% (non-condensing)
|
|
|
|
File Name |
Issue Date |
Language |
File Size |
|
Temperature Controller Operational Manual
|
9/17/2007
|
English
|
1.69M
|
|
DTB Quick Start Manual
|
1/8/2007
|
English
|
1.23M
|
|
|
File Name |
Issue Date |
Language |
File Size |
|
Delta Temperature Controller Brochure
|
2/19/2010
|
English
|
4.34M
|
|
|
File Name |
Issue Date |
Language |
File Size |
|
DTCOM Software
|
3/19/2009
|
English
|
0.69M
|
|
|
Delta Products Corporation
P.O. Box 12173
5101 Davis Drive
Research Triangle Park, NC 27709
Phone: 919-767-3813
Fax: 919-767-3969