VFD-M
The VFD-M drive is a Sensorless Vector Micro AC drive that provides advanced motor speed control in a compact design. The VFD-M Series is an IP20 rated drive ranging from fractional to 10 hp with input voltages ranging from 110VAC to 575VAC. The VFD-M series drives are used in many applications including: Drilling Machines, Food Processing, Grinding Machines, Milling Machines (CNC), Packaging Machines, Residential Elevators, Spindle Motors , and Treadmills to name a few.
|
|
|
|
VFD-M Specifications
|
Voltage Class
|
115V Class
|
|
Model Number VFD-XXXM
|
002
|
004
|
007
|
|
Max. Applicable Motor Output (kW)
|
0.2
|
0.4
|
0.75
|
|
Max. Applicable Motor Output (hp)
|
0.25
|
0.5
|
1.0
|
|
Output Rating
|
Rated Output Capacity (kVA)
|
0.6
|
1.0
|
1.6
|
|
Rated Output Current (A)
|
1.6
|
2.5
|
4.2
|
|
Maximum Output Voltage (V)
|
3-Phase proportion to twice the input voltage
|
|
Output Frequency (Hz)
|
0.1~400 Hz
|
|
Carrier Frequency (kHz)
|
1-15
|
|
Input Rating
|
Rated Input Current (A)
|
Single phase
|
|
6
|
9
|
16
|
|
Rated Voltage, Frequency
|
Single phase, 100-120 VAC, 50/60Hz
|
|
Voltage Tolerance
|
10% (90-132VAC)
|
|
Frequency Tolerance
|
5% (47~63Hz)
|
|
Cooling Method
|
Fan Cooled
|
|
Weight (kg)
|
1.5
|
1.5
|
1.5
|
|
Voltage Class
|
230V Class
|
|
Model Number VFD-XXXM
|
004
|
007
|
015
|
022
|
037
|
055
|
|
Max. Applicable Motor Output (kW)
|
0.4
|
0.75
|
1.5
|
2.2
|
3.7
|
5.5
|
|
Max. Applicable Motor Output (hp)
|
0.5
|
1.0
|
2.0
|
3.0
|
5.0
|
7.5
|
|
Output Rating
|
Rated Output Capacity (kVA)
|
1.0
|
1.9
|
2.7
|
3.8
|
6.5
|
9.5
|
|
Rated Output Current (A)
|
2.5
|
5.0
|
7.0
|
10
|
17
|
25
|
|
Maximum Output Voltage (V)
|
3-Phase proportional to input voltage
|
|
Output Frequency (Hz)
|
0.1~400 Hz
|
|
Carrier Frequency (kHz)
|
1-15
|
|
Input Rating
|
Rated Input Current (A)
|
Single/3-phase
|
3-phase
|
|
6.3/2.9
|
11.5/7.6
|
15.7/8.8
|
27/12.5
|
19.6
|
28
|
|
Input Current for 1-phase Models when Using 3-phase Power
|
3.2
|
6.3
|
9.0
|
12.5
|
--
|
--
|
|
Rated Voltage, Frequency
|
Single/3-phase
200-240 VAC, 50/60Hz
|
3-phase
200-240VAC, 50/60Hz
|
|
Voltage Tolerance
|
10% (180~264 VAC)
|
|
Frequency Tolerance
|
5% (47~63 Hz)
|
|
Cooling Method
|
Fan Cooled
|
|
Weight (kg)
|
2.2/1.5
|
2.2/1.5
|
2.2/1.5
|
3.2/2.2
|
3.2
|
3.2
|
|
Voltage Class
|
460V Class
|
|
Model Number VFD-XXXM
|
007
|
015
|
022
|
037
|
055
|
075
|
|
Max. Applicable Motor Output (kW)
|
0.75
|
1.5
|
2.2
|
3.7
|
5.5
|
7.5
|
|
Max. Applicable Motor Output (hp)
|
1.0
|
2.0
|
3.0
|
5.0
|
7.5
|
10
|
|
Output Rating
|
Rated Output Capacity (kVA)
|
2.3
|
3.1
|
3.8
|
6.2
|
9.9
|
13.7
|
|
Rated Output Current (A)
|
3.0
|
4.0
|
5.0
|
8.2
|
13
|
18
|
|
Maximum Output Voltage (V)
|
3-phase Proportional to Input Voltage
|
|
Output Frequency (Hz)
|
0.1~400 Hz
|
|
Carrier Frequency (kHz)
|
1-15
|
|
Input Rating
|
Rated Input Current (A)
|
3-phase
|
|
4.2
|
5.7
|
6.0
|
8.5
|
14
|
23
|
|
Rated Voltage, Frequency
|
3-phase 380-480 VAC, 50/60Hz
|
|
Voltage Tolerance
|
10% (342~528 VAC)
|
|
Frequency Tolerance
|
5% (47~63 Hz)
|
|
Cooling Method
|
Fan Cooled
|
|
Weight (kg)
|
1.5
|
1.5
|
2.0
|
3.2
|
3.2
|
3.3
|
|
Voltage Class
|
575V Class
|
|
Model Number VFD-XXXM
|
007
|
015
|
022
|
037
|
055
|
075
|
|
Max. Applicable Motor Output (kW)
|
0.75
|
1.5
|
2.2
|
3.7
|
5.5
|
7.5
|
|
Max. Applicable Motor Output (hp)
|
1.0
|
2.0
|
3.0
|
5.0
|
7.5
|
10
|
|
Output Rating
|
Rated Output Capacity (kVA)
|
1.7
|
3.0
|
4.2
|
6.6
|
9.9
|
12.2
|
|
Rated Output Current (A)
|
1.7
|
3.0
|
4.2
|
6.6
|
9.9
|
12.2
|
|
Maximum Output Voltage (V)
|
3-phase Proportional to Input Voltage
|
|
Output Frequency (Hz)
|
0.1~400 Hz
|
|
Carrier Frequency (kHz)
|
1-10
|
|
Input Rating
|
|
3-phase
|
|
|
|
|
|
|
12.9
|
|
Rated Voltage, Frequency
|
3-phase 500-600 VAC, 50/60Hz
|
|
Voltage Tolerance
|
-15% ~ +10% (425~660 V)
|
|
Frequency Tolerance
|
5% (47~63 Hz)
|
|
Cooling Method
|
Fan Cooled
|
|
Weight (kg)
|
1.5
|
1.5
|
2.0
|
3.2
|
3.2
|
3.3
|
|
General Specifications
|
|
Control Characteristics
|
Control System
|
SPWM (Sinusoidal Pulse Width Modulation) control (V/F or sensorless vector control)
|
|
Freq. Setting Resolution
|
0.1Hz
|
|
Output Frequency Resolution
|
0.1Hz
|
|
Torque Characteristics
|
Including the auto-torque, auto-slip compensation; starting torque can be 150% at 5.0Hz
|
|
Overload Endurance
|
150% of rated current for 1 minute
|
|
Skip Frequency
|
Three zones, settings range 0.1-400Hz
|
|
Accel/Decel Time
|
0.1 to 600 seconds (4 Independent settings for Accel/Decel Time)
|
|
Stall Prevention Level
Frequency Setting
|
20 to 200%, Setting of Rated Current
|
|
DC Injection Braking
|
Operation frequency 0-60Hz, output 0-100% rated current
Start time 0-5 seconds, stop time 0-25 seconds
|
|
Braking Torque
|
Approx. 20% (up to 125% possible with option brake resistor or brake unit externally mounted, 1-15HP braking transistor built-in)
|
|
V/F Pattern
|
Adjustable V/F pattern
|
|
Operating Characteristics
|
Frequency Setting
|
Keypad
|
Setting by
|
|
External Signal
|
Potentiometer-5KW/0.5W, 0 to +10VDC, 4 to 20mA RS-485 interface; Multi-Function Inputs 0 to 5 (7 steps, Jog, up/down)
|
|
Operation Setting Signal
|
Keypad
|
Set by RUN, STOP
|
|
External Signal
|
M0 to M5 can be combined to offer various modes of operation, RS-485 serial interface (MODBUS).
|
|
Multi-Function Input Signal
|
Multi-step selection 0 to 7, Jog, accel/decel inhibit, first to forth accel/decel switches, counter, PLC operation, external Base Block (NC, NO), auxiliary motor control is invalid, selections, driver reset, UP/DOWN key settings, sink/source selection
|
|
Multi-Function Output Indication
|
AC drive operating, frequency attained, non-zero, base block, fault indication, local/remote indication, PLC operation indication, auxiliary motor output, driver is ready, overheat alarm, emergency stop
|
|
Analog Output Signal
|
Analog frequency/current signal output.
|
|
Alarm Output Contact
|
1 Form C contact or open collector output
|
|
Operation Functions
|
AVR, S-Curve, over-voltage, over-current stall prevention, fault records, adjustable carrier frequency, DC braking, momentary power loss restart, auto tuning, frequency limits, parameter Lock/Reset, vector control, counter, PID Control, PLC, MODBUS communication, reverse Inhibition, abnormal reset, abnormal re-start, digital frequency output, sleep/revival function, 1st/2nd frequency source selections
|
|
Protection Functions
|
Self-testing, over voltage, over current, under voltage, overload, overheating, external fault, electronic thermal, ground fault.
|
|
Display Keypads
|
6-key, 4-digit, 7-segment LED, 4 status LEDs, master frequency, output frequency, output current, custom units, parameter values for setup, review and faults, RUN, STOP, RESET, FWD/REV
|
|
Built-in Brake Chopper
|
Built-in for all models
|
|
Environmental Conditions
|
Protection Level
|
IP20
|
|
Pollution Degree
|
2
|
|
Installation Location
|
Altitude 1,000 m or lower, keep from corrosive gasses, liquid and dust
|
|
Ambient Temperature
|
-10oC to 40oC (-10oC to 50oC without blind plate)
Non-Condensing and not frozen
|
|
Storage/Transportation Temperature
|
-20oC to 60oC
|
|
Ambient Humidity
|
Below 90% RH (non-condensing)
|
|
Vibration
|
9.80665m/s2 (1G) less than 20Hz, 5.88m/s2 (0.6G) at 20 to 50Hz
|
|
Approvals
|

|
Note: Do not attempt to connect a single-phase power source to a three-phase models drive. However it is acceptable to connect two wires of a three-phase power source to a single-phase drive.
|
|
|
File Name |
Issue Date |
Language |
File Size |
|
VFD-M
|
5/19/2008
|
English
|
2.51M
|
|
VFD-M Quick Start Manual
|
5/19/2008
|
English
|
0.48M
|
|
|
File Name |
Issue Date |
Language |
File Size |
|
VFD-M Brochure
|
10/21/2005
|
English
|
2.39M
|
|
|
File Name |
Issue Date |
Language |
File Size |
|
VFD Software User Manual
|
11/15/2007
|
English
|
5.95M
|
|
VFD Software V.1.42
|
12/30/2008
|
English
|
28.97M
|
|
|
Delta Products Corporation
P.O. Box 12173
5101 Davis Drive
Research Triangle Park, NC 27709
Phone: 919-767-3813
Fax: 919-767-3969
Email: IABUsupport@delta-corp.com