VFD-EL
The VFD-EL series is Delta’s newest VFD family member. The VFD-EL is an IP20 rated drive ranging from fractional to 5 hp with input voltages ranging from 110VAC to 460VAC.The compact multi-functional drive series has a high-efficiency thermal design which allows for “zero stack” and din rail mount for space saving optimization. The optional Fieldbus Modules provide connection to a variety of networks used in many applications including: Blowers, Conveyer Systems, Simple Processing Equipment, Small Fan and Pump and Washing Machines to name a few.
|
|
|
|
VFD-EL Specifications
|
Voltage Class
|
115V Class
|
|
Model Number VFD-XXXEL
|
002
|
004
|
007
|
|
Max. Applicable Motor Output (kW)
|
0.2
|
0.4
|
0.75
|
|
Max. Applicable Motor Output (hp)
|
0.25
|
0.5
|
1.0
|
|
Output Rating
|
Rated Output Capacity (kVA)
|
0.6
|
1.0
|
1.6
|
|
Rated Output Current (A)
|
1.6
|
2.5
|
4.2
|
|
Maximum Output Voltage (V)
|
3-Phase Proportional to Twice the Input Voltage
|
|
Output Frequency (Hz)
|
0.1~600 Hz
|
|
Carrier Frequency (kHz)
|
2-12
|
|
Input Rating
|
Rated Input Current (A)
|
6.4
|
9
|
18
|
|
Rated Voltage/Frequency
|
Single phase, 100-120V, 50/60Hz
|
|
Voltage Tolerance
|
10%(90~132 V)
|
|
Frequency Tolerance
|
5%(47~63 Hz)
|
|
Cooling Method
|
Natural Cooling
|
|
Weight (kg)
|
1.1
|
1.1
|
1.4
|
|
Voltage Class
|
230V Class
|
|
Model Number VFD-XXXEL
|
002
|
004
|
007
|
015
|
022
|
037
|
|
Max. Applicable Motor Output (kW)
|
0.2
|
0.4
|
0.75
|
1.5
|
2.2
|
3.7
|
|
Max. Applicable Motor Output (hp)
|
0.25
|
0.5
|
1.0
|
2.0
|
3.0
|
5.0
|
|
Output Rating
|
Rated Output Capacity (kVA)
|
0.6
|
1.0
|
1.6
|
2.9
|
4.2
|
6.5
|
|
Rated Output Current (A)
|
1.6
|
2.5
|
4.2
|
7.5
|
11.0
|
17
|
|
Maximum Output Voltage (V)
|
3-Phase Proportional to Input Voltage
|
|
Output Frequency (Hz)
|
0.1~600 Hz
|
|
Carrier Frequency (kHz)
|
2-12
|
|
Input Rating
|
XXXEL
21A
|
Rated Input Current (A)
|
4.9
|
6.5
|
9.5
|
15.7
|
24
|
--
|
|
Rated Voltage/Frequency
|
1-phase, 200-240 V, 50/60Hz
|
|
XXXEL
23A
|
Rated Input Current (A)
|
1.9
|
2.7
|
4.9
|
9
|
15
|
20.6
|
|
Rated Voltage/Frequency
|
3-phase, 200-240V, 50/60Hz
|
|
Voltage Tolerance
|
10%(180~264 V)
|
|
Frequency Tolerance
|
5%(47~63 Hz)
|
|
Cooling Method
|
Natural Cooling
|
Fan Cooling
|
|
Weight (kg)
|
1.2
|
1.2
|
1.2
|
1.7
|
1.7
|
1.7
|
|
Voltage Class
|
460V Class
|
|
Model Number VFD-XXXEL
|
004
|
007
|
015
|
022
|
037
|
|
Max. Applicable Motor Output (kW)
|
0.4
|
0.75
|
1.5
|
2.2
|
3.7
|
|
Max. Applicable Motor Output (hp)
|
0.5
|
1.0
|
2.0
|
3.0
|
5.0
|
|
Output Rating
|
Rated Output Capacity (kVA)
|
1.2
|
2.0
|
3.3
|
4.4
|
6.8
|
|
Rated Output Current (A)
|
1.5
|
2.5
|
4.2
|
5.5
|
8.2
|
|
Maximum Output Voltage (V)
|
3-Phase Proportional to Input Voltage
|
|
Output Frequency (Hz)
|
0.1~600 Hz
|
|
Carrier Frequency (kHz)
|
2-12
|
|
Input Rating
|
Rated Input Current (A)
|
1.8
|
3.2
|
4.3
|
7.1
|
9.0
|
|
Rated Voltage/Frequency
|
3-phase, 380-480V, 50/60Hz
|
|
Voltage Tolerance
|
10%(342~528V)
|
|
Frequency Tolerance
|
(47~63Hz)
|
|
Cooling Method
|
Natural Cooling
|
Fan Cooling
|
|
Weight (kg)
|
1.2
|
1.2
|
1.2
|
1.7
|
1.7
|
|
General Specifications
|
|
Control Characteristics
|
Control System
|
SPWM(Sinusoidal Pulse Width Modulation) control (V/f control)
|
|
Frequency Setting Resolution
|
0.01Hz
|
|
Output Frequency Resolution
|
0.01Hz
|
|
Torque Characteristics
|
Including the auto-torque/auto-slip compensation; starting torque can be 150% at 5.0Hz
|
|
Overload Endurance
|
150% of rated current for 1 minute
|
|
Skip Frequency
|
Three zones, setting range 0.1-600Hz
|
|
Accel/Decel Time
|
0.1 to 600 seconds (2 Independent settings for Accel/Decel time)
|
|
Stall Prevention Level
|
Setting 20 to 250% of rated current
|
|
DC Brake
|
Operation frequency 0.1-600.0Hz, output 0-100% rated current
Start time 0-60 seconds, stop time 0-60 seconds
|
|
Regenerated Brake Torque
|
Approx. 20% (up to 125% possible with optional brake resistor or externally mounted brake unit, 1-15hp (0.75-11kW) models have brake chopper built-in)
|
|
V/f Pattern
|
Adjustable V/f pattern
|
|
Operating Characteristics
|
Frequency Setting
|
Keypad
|
Setting by 
|
|
External Signal
|
Potentiometer-5kW/0.5W, 0 to +10VDC, 4 to 20mA, RS-485 interface; Multi-function Inputs 3 to 6 (15 steps, Jog, up/down)
|
|
Operation Setting Signal
|
Keypad
|
Set by RUN and STOP
|
|
External Signal
|
2 wires/3 wires ((MI1, MI2, MI3)), JOG operation, RS-485 serial interface (MODBUS), programmable logic controller
|
|
Multi-function Input Signal
|
Multi-step selection 0 to 15, Jog, accel/decel inhibit, 2 accel/decel switches, counter, external Base Block, ACI/AVI selections, driver reset, UP/DOWN key settings, NPN/PNP input selection
|
|
Multi-function Output Indication
|
AC drive operating, frequency attained, zero speed, Base Block, fault indication, overheat alarm, emergency stop and status selections of input terminals
|
|
Analog Output Signal
|
Output frequency/current
|
|
Operation Functions
|
AVR, accel/decel S-Curve, over-voltage/over-current stall prevention, 5 fault records, reverse inhibition, momentary power loss restart, DC brake, auto torque/slip compensation, auto tuning, adjustable carrier frequency, output frequency limits, parameter lock/reset, PID control, external counter, MODBUS communication, abnormal reset, abnormal re-start, power-saving, fan control, sleep/wake frequency, 1st/2nd frequency source selections, 1st/2nd frequency source combination, NPN/PNP selection
|
|
Protection Functions
|
Over voltage, over current, under voltage, external fault, overload, ground fault, overheating, electronic thermal, IGBT short circuit, PTC
|
|
Display Keypad (optional)
|
6-key, 7-segment LED with 4-digit, 4 status LEDs, master frequency, output frequency, output current, custom units, parameter values for setup and lock, faults, RUN, STOP, RESET, FWD/REV
|
|
Built-in EMI Filter
|
For 230V 1-phase and 460V 3-phase models.
|
|
Enviromental Conditions
|
Enclosure Rating
|
IP20
|
|
Pollution Degree
|
2
|
|
Installation Location
|
Altitude 1,000 m or lower, keep from corrosive gasses, liquid and dust
|
|
Ambient Temperature
|
-10oC to 50oC (40oC for side-by-side mounting) Non-Condensing and not frozen
|
|
Storage/ Transportation Temperature
|
-20 oC to 60 oC
|
|
Ambient Humidity
|
Below 90% RH (non-condensing)
|
|
Vibration
|
9.80665m/s2 (1G) less than 20Hz, 5.88m/s2 (0.6G) at 20 to 50Hz
|
|
Approvals
|

|
|
|
|
File Name |
Issue Date |
Language |
File Size |
|
VFD-EL
|
4/18/2008
|
English
|
3.67M
|
|
VFD-EL Quick Start Manual
|
9/10/2008
|
English
|
0.66M
|
|
|
File Name |
Issue Date |
Language |
File Size |
|
VFD-EL Brochure
|
9/13/2007
|
English
|
3.65M
|
|
|
File Name |
Issue Date |
Language |
File Size |
|
VFD Software User Manual
|
11/15/2007
|
English
|
5.95M
|
|
VFD Software V.1.42
|
12/30/2008
|
English
|
28.97M
|
|
|
Delta Products Corporation
P.O. Box 12173
5101 Davis Drive
Research Triangle Park, NC 27709
Phone: 919-767-3813
Fax: 919-767-3969
Email: IABUsupport@delta-corp.com
Hours: 8 a.m. to 7 p.m. EST
|
|
|