VFD-F
The VFD-F series is a Variable Torque rated AC Drive that was specifically designed for fan and pump applications ranging from 1 to 300 hp. This series offers the capability of connecting four motors at the same time and running them consecutively. PID, Sleep/Wake, and undercurrent protection are additional features of the VFD-F series drive allowing it to be used in many applications including: Air Conditioning Systems, Blowers, Fountains, Water/Wastewater Treatment Systems, and Ventilation Systems to name a few.
|
|
|
|
VFD-F Specifications
| Voltage Class |
230V Class
|
| Model Number VFD-XXX F23X |
007
|
015
|
022
|
037
|
055
|
075
|
110
|
150
|
185
|
220
|
300
|
370
|
| Max. Applicable Motor Output (kW) |
0.75
|
1.5
|
2.2
|
3.7
|
5.5
|
7.5
|
11
|
15
|
18.5
|
22
|
30
|
37
|
| Max. Applicable Motor Output (HP) |
1.0
|
2.0
|
3.0
|
5.0
|
7.5
|
10
|
15
|
20
|
25
|
30
|
40
|
50
|
| Output Rating |
Rated Output Capacity (KVA) |
1.9
|
2.5
|
4.2
|
6.5
|
9.5
|
12.5
|
18.3
|
24.7
|
28.6
|
34.3
|
45.7
|
55
|
| Rated Output Current (A) |
5.0
|
7.0
|
11
|
17
|
25
|
33
|
49
|
65
|
75
|
90
|
120
|
145
|
| Maximum Output Voltage (V) |
Proportional to Input Voltage
|
| Rated Frequency (Hz) |
0.10-120.00Hz
|
| Carrier Frequency (kHz) |
4-10
|
3-9
|
2-6
|
| Input Rating |
Rated Input Current (A) |
5.7
|
7.6
|
15.5
|
20.6
|
26
|
34
|
50
|
60
|
75
|
90
|
110
|
142
|
| Rated Voltage |
3-phase 180-264 V
|
| Frequency Tolerance |
47 – 63 Hz |
| Voltage Class |
460V Class
|
|
Model Number
VFD-XXX F43X
|
007
|
015
|
022
|
037
|
055
|
075
|
110
|
150
|
185
|
220
|
300
|
370
|
450
|
550
|
750
|
900
|
1100
|
1320
|
1600
|
1850
|
2200
|
Max. Applicable
Motor Output (kW) |
0.75
|
1.5
|
2.2
|
3.7
|
5.5
|
7.5
|
11
|
15
|
18.5
|
22
|
30
|
37
|
45
|
55
|
75
|
90
|
110
|
132
|
160
|
185
|
220
|
Max. Applicable Motor
Output (HP) |
1.0
|
2.0
|
3.0
|
5.0
|
7.5
|
10
|
15
|
20
|
25
|
30
|
40
|
50
|
60
|
75
|
100
|
125
|
150
|
175
|
215
|
250
|
300
|
Output
Rating |
Rated Output
Capacity (KVA) |
2.3
|
3.2
|
4.2
|
6.5
|
10
|
14
|
18
|
25
|
29
|
34
|
46
|
56
|
69
|
84
|
114
|
137
|
168
|
198
|
236
|
281
|
350
|
Rated Output
Current (A) |
2.7
|
4.2
|
5.5
|
8.5
|
13
|
18
|
24
|
32
|
38
|
45
|
60
|
73
|
91
|
110
|
150
|
180
|
220
|
260
|
310
|
370
|
460
|
Maximum Output
Voltage (V) |
Proportional to Input Voltage
|
Rated Frequency
(Hz) |
0.10-120.00Hz
|
Carrier Frequency
(kHz) |
4-10
|
3-9
|
2-6
|
Input
Rating |
Rated Input
Current (A) |
3.2
|
4.3
|
5.9
|
11.2
|
14
|
19
|
25
|
32
|
39
|
49
|
60
|
73
|
91
|
120
|
160
|
160
|
200
|
240
|
300
|
380
|
400
|
| Rated Voltage |
3-phase 342-528 V
|
Frequency
Tolerance |
47 – 63 Hz
|
| General Specifications |
Control Characteristics |
Control System |
SPWM (Sinusoidal Pulse Width Modulation, carrier frequency 2-10kHz)
|
| Output Frequency Resolution |
0.01Hz
|
| Torque Characteristics |
Including the auto-torque, auto-slip compensation; starting torque can be 150% at 1.0Hz
|
| Overload Endurance |
120% of rated current for 1 minute
|
| Accel/Decel Time |
1-36000/0.1-3600.0/0.01-360.00 seconds (3 Independent settings for Accel/Decel Time)
|
| V/f Pattern |
Adjustable V/f pattern
|
| Stall Prevention Level |
20 to 150%, Setting of Rated Current
|
| Operating Characteristics |
Frequency Setting |
Keypad |
Setting by 
|
| External Signal |
1 set of AVI analog voltage DC0-+10V/0-+5V, 2 sets of ACI analog current 0/4-20mA,
15 Multi-Function Inputs, RS-485 interface (MODBUS), External terminals UP/DOWN Key
|
| Operation Setting Signal |
Keypad |
Set by RUN, STOP and JOG
|
| External Signal |
Operation by FWD, REV, JOG and communication operation
|
| Multi-Function Input Signal |
Multi-step selection 0 to 15, Jog, accel/decel inhibit, first to forth accel/decel switches, counter, external Base Block (NC, NO), JOG, auxiliary motor start/maintenance
|
| Multi-Function Output Indication |
AC Drive Operating, Frequency Attained, Desired Frequency Attained, Zero speed, Base Block, Fault Indication, Local/Remote indication, and Auxiliary Motor Output
|
| Analog Output Signal |
2 sets of Analog frequency/current signal output
|
| Other Functions |
AVR, 2 kinds of S-Curve, Over-Voltage, Over-Current Stall Prevention, Fault Records, Reverse inhibition, DC Brake, Momentary Power Loss restart, Auto torque and slip compensation, PID Control, Parameter Lock/Reset, Frequency Limits, Adjustable Carrier Frequency, 4 sets of Fan & Pump Control,
|
| Protection |
Self-testing, Over Voltage, Over Current, Under Voltage, Overload, Overheating, External Fault, Electronic thermal, Ground Fault, Phase-loss
|
| Built-in Reactor |
DC Reactor: 25~215HP
AC Reactor: 250~300HP
|
| Built-in Brake Chopper |
1~20HP
|
| Cooling Methods |
Forced Fan-cooled
|
|
Environment
|
Installation Location |
Altitude 1,000 m or lower, keep from corrosive gasses, liquid and dust
|
| Pollution Degree |
2
|
| Ambient Temperature |
-10oC to 40oC Non-Condensing and not frozen
|
| Storage/ Transportation Temperature |
-20oC to 60oC
|
| Ambient Humidity |
Below 90% RH (non-condensing)
|
| Vibration |
9.80665m/s2 (1G) less than 20Hz, 5.88m/s2 (0.6G) at 20 to 50Hz
|
|
|
|
File Name |
Issue Date |
Language |
File Size |
|
VFD-F
|
8/1/2008
|
English
|
3.31M
|
|
VFD-F Quick Start Manual
|
8/2/2008
|
English
|
1.10M
|
|
|
File Name |
Issue Date |
Language |
File Size |
|
VFD-F Brochure
|
6/9/2006
|
English
|
2.46M
|
|
|
File Name |
Issue Date |
Language |
File Size |
|
VFD Software User Manual
|
11/15/2007
|
English
|
5.95M
|
|
VFD Software V.1.42
|
12/30/2008
|
English
|
28.97M
|
|
|
Delta Products Corporation
P.O. Box 12173
5101 Davis Drive
Research Triangle Park, NC 27709
Phone: 919-767-3813